One of the components you need for a PROFIBUS installation
ist the communication interface from Hilscher.
For making the configuration you have to install a software tool,
also from Hilscher, the "System Configurator" SyCon. The software
must be licensed. Please contact www.hilscher.com
for further details.
The minimum hardware consists of a general purpose PC with an interface
CIF30-FMS from Hilscher, an S7 system (Siemens) with a module CP443-5
Basic and a profibus connection cable.
For programming and testing a NULL modem cable is required for downloading
the parameters to the CIF.
Furthermore for programming the S7 you may want to use a MPI-PC adapter,
which allows access to the programming port of the S7-CPU from the
serial port of a laptop.
Making a connection between a PC equipped
with an FMS interface from Hilscher (see www.hilscher.com)
and a PLC S7-400 requires the availability of the system configuration
utility SyCon.
SyCon may be purchased directly from Hilscher and must be licensed.
General settings
Do not change the settings for "Little
Endian", since this will influence the data representation inside
the system software!
BTW: Technical manuals must not be that serious all the time. ;-)
Define a unique station address for
each member on that bus.
Check all parameters in order to coordinate
them with the corresponding parameters of the S7 controller.
Check all parameters in order to coordinate
them with the corresponding parameters of the S7 controller.
In case of a PROFIBUS-DP system with one master the only parameter
which must be selected is the baud rate. If there is a FMS device
on the bus or more than one master the parameter must be edited manually.
The baud rate of the PROFIBUS is common for all
bus devices. Changing the baud rate has the consequence that all
other parameters will be re-calculated. The System Configurator
checks if the baud rate is supported by all configured devices on
basis of the entries in the GSD file. If the System Configurator
finds at least one device in the configuration that does not support
the selected baud rate an error message appears.
You can check the actual parameters if you open the Edit Bus Parameter
window with the button Edit. Some of the parameters can be changed
individually. Please note if you make any changes in the bus parameters
the parameter for the field Optimize must be changed from by SyCon
to by User. Caution: Changing the bus parameter individually can force
a communication break.
The Highest Station Address is the highest bus address up to which
the master will search for other active master stations to pass
the send permission. This value should not be set below the master
address.
With the flag Auto Clear it is possible to select a global error
flag. The DP-Master supervises the process data transfer of all
DP-slaves with a timer. If no successful data transfer can be established
to one of these stations or an existing communication breaks during
one data control time interval with activated option Auto clear
modus on, the DP-Master leaves the user data, transfer and switches
the outputs of all assigned DP-slaves to the fail-safe state.
For PROFIBUS-FMS are two profiles available:
- Siemens S7 Profile FMS
- Siemens S5 Profile FMS
Select profile S5 when using a Siemens PLC S5, select profile S7
when using a Siemens PLC S7 in the PROFIBUS-FMS network.
Defining communication objects
Communication objects have to be defined,
if you want to use the FMS monitor section of SyCon. Make sure, you
enter the exact type and size of the variable.
Using FMS monitor
The FMS monitor allows to check the
communication with the adjacent partner, e.g. the S7 PLC. You may
read or write to a defined object. Attention: be careful not to write
to an object in a live installation. This may be hazardous to the
connected modules!